Certificate/Reg.-No. | 968/FSA 1064.00/15 |
Type of Certificate | FSA Certificate |
Certificate Holder | Frames Energy Systems B.V. |
Product Category | Safety Instrumented Systems / SRECS / Safety Functions > HIPPS |
Subject | High Integrity Protection System - for Petrobras FPSO P-62 Design, Engineering (including IFAT) corresponding life cycle documentation. |
Type Designation | Frames ref: VO 29533 SIS 1: Protection against overpressure |
Codes and Standards |
|
Scope and Result | Stage 2 assessment IEC 61511 SLC for the Safety Instrumented System: HIPPS for FPSO P-62 The documented design, engineering and fault avoidance and validation activities comply with the requirements of IEC 61511 (Phase 4 of the safety life cycle) for SIL 3. SIF 1 calculated PFDavg=4.6E-04 (RRF=2170) claiming a proof test interval of 4380 h, a MTTR of 72 h and overhaul period of 5 years. |
Specific Provisions | The project related safety manual (P29533-EF-SMA-001) and the safety documentation delivered by the component suppliers have to be observed. A partial stroke test shall be performed every 3 months. Positive effects on the system reliability due to partial stroke testing are not taken into account in the PFDavg calculation. Any change in type or firmware of used hard- or software modules and changes in the application logic requires a reconsideration of the whole system. The validation of the target system including SAT is not covered by this assessment. |
Valid Until | no expiry date |
Appendixes | n/a |
Download Certificate | 968_FSA_1064_00_15_en_el.pdf |
Certificate/Reg.-No. | Certificate Holder | Product Category | Product Tested | Type Designation | Details |
---|
968/FSA 1064.00/15 | Frames Energy Systems B.V. | Safety Instrumented Systems / SRECS / Safety Functions → HIPPS | High Integrity Protection System - for Petrobras FPSO P-62 Design, Engineering (including IFAT) corresponding life cycle documentation. | Frames ref: VO 29533 SIS 1: Protection against overpressure | View Details | View PDF |
Remark: In case of missing entries this is due to restrictions by the certificate holder