Certificate/Reg.-No. | 968/FSA 1137.00/18 |
Type of Certificate | FSA Certificate |
Certificate Holder | Frames Energy Systems B.V. |
Manufacturer | Frames Energy Systems B.V. |
Product Category | Safety Instrumented Systems / SRECS / Safety Functions > HIPPS |
Subject | Design and engineering of the HIPPS of Höegh S2220 for Wärtsilä Oil & Gas Systems AS. |
Type Designation | FRAMES Ref.: EVO 102818 / Höegh S2220 SIF 1.1 to SIF 1.3: Protection of each regasification Train 1 to 3 against high pressure in the downstream equipment due to a blocked outlet of each individual discharge header. SIF 1.4: Protection of all regasification Trains 1 to 3 against high pressure in the downstream equipment due to a blocked outlet of the common output header. |
Codes and Standards |
|
Scope and Result | Stage 2 assessment acc. to IEC 61511 for the Safety Instrumented Systems (incl. IFAT): HIPPS of Höegh SN2220 for Wärtsilä Oil & Gas Systems AS. The documented design, engineering and fault avoidance and validation activities comply with the requirements of IEC 61511 (Phase 4 of Safety Life-Cycle) for SIL 3. |
Specific Provisions | The project related safety manual (P102818-EF-SMA-001) and the safety documentation delivered by the component suppliers have to be observed. Any change in type or firmware of used hard- or software modules and changes in the application logic requires a reconsideration of the whole system. The validation of the target system including SAT is not covered by this assessment. |
Valid Until | no expiry date |
Appendixes | n/a |
Download Certificate | 968_FSA_1137_00_18_en_el.pdf |
Certificate/Reg.-No. | Certificate Holder | Product Category | Product Tested | Type Designation | Details |
---|
968/FSA 1137.00/18 | Frames Energy Systems B.V. | Safety Instrumented Systems / SRECS / Safety Functions → HIPPS | Design and engineering of the HIPPS of Höegh S2220 for Wärtsilä Oil & Gas Systems AS. | FRAMES Ref.: EVO 102818 / Höegh S2220 SIF 1.1 to SIF 1.3: Protection of each regasification Train 1 to 3 against high pressure in the downstream equipment due to a blocked outlet of each individual discharge header. SIF 1.4: Protection of all regasification Trains 1 to 3 against high pressure in the downstream equipment due to a blocked outlet of the common output header. | View Details | View PDF |
Remark: In case of missing entries this is due to restrictions by the certificate holder