Certificate/Reg.-No. | 968/FSP 1388.01/19 |
Type of Certificate | A-FS&CS Certificate |
Certificate Holder | Endress+Hauser SE + Co. KG |
Manufacturer | Endress+Hauser SE + Co. KG |
Product Category | Sensors, Transmitters, Guards > for Filling Level |
Subject | Level monitor |
Type Designation | Liquiphant FTL51B |
Codes and Standards |
|
Scope and Result | For the safety functions MIN or MAX level monitoring the devices comply with the requirements of IEC 61508 (Hardware safety integrity SIL 2 and systematic capability SIL 3) and can be used in applications up to SIL 2 (HFT=0) resp. SIL 3 (HFT=1) acc. to IEC 61508. For the safety function MAX level monitoring the devices comply with the requirements of ISO 13849-1 Category 2 / PL d and can be used in applications up to PL d acc. to ISO 13849-1. For the safety function MIN level monitoring the devices comply with the requirements of ISO 13849-1 Category 1 / PL c and can be used in applications up to PL c acc. to ISO 13849-1. |
Specific Provisions | The instructions of the associated Operating Manual and Safety Manual shall be considered. |
Valid Until | 2024-09-25 |
Appendixes | n/a |
Download Certificate | 968_FSP_1388_01_19_de_en_el.pdf |
Certificate/Reg.-No. | Certificate Holder | Product Category | Product Tested | Type Designation | Details |
---|
968/FSP 1388.01/19 | Endress+Hauser SE + Co. KG | Sensors, Transmitters, Guards → for Filling Level | Level monitor | Liquiphant FTL51B | View Details | View PDF |
Remark: In case of missing entries this is due to restrictions by the certificate holder