Certificate/Reg.-No. | 968/FSP 2541.00/23 |
Type of Certificate | A-FS&CS Certificate |
Certificate Holder | ABB Engineering (Shanghai) Ltd. |
Manufacturer | ABB Engineering (Shanghai) Ltd. |
Product Category | Sensors, Transmitters, Guards > for Furnaces/Burners |
Subject | Flame Detector |
Type Designation | Uvisor SF910i-(LOS/FOC)-(IR/UV/UVIR/PYR)-(T/TX/TL/Q/QC/QE) |
Codes and Standards |
|
Scope and Result | The flame detector comply with the requirements of EN 298 for the use in industrial appliances and SC3, SIL 2 acc. to lEC 61508. It can be used in HFT = 0 in applications up to SIL 2 and in HFT=1 configuration in applications up to SIL 3. Where the flame detector is used in applications according to the standard EN 298, the flame detector need to be used in the 1oo2 in structure (two flame detectors where the two outputs relays is in series). |
Specific Provisions | The instructions of the associated Installation, Operation and Safety Manual shall be considered. |
Valid Until | no expiry date |
Appendixes | n/a |
Download Certificate | 968_FSP_2541_00_23_en_el.pdf |
Certificate/Reg.-No. | Certificate Holder | Product Category | Product Tested | Type Designation | Details |
---|
968/FSP 2541.00/23 | ABB Engineering (Shanghai) Ltd. | Sensors, Transmitters, Guards → for Furnaces/Burners | Flame Detector | Uvisor SF910i-(LOS/FOC)-(IR/UV/UVIR/PYR)-(T/TX/TL/Q/QC/QE) | View Details | View PDF |
Remark: In case of missing entries this is due to restrictions by the certificate holder